Key Features
- Fire-rated counter shutter that complies with NFPA 80
- UL 3-hour Class A label for masonry fire walls (FM label optional), or UL 1 1/2-hour Class B label for drywall and stud walls
- Fusible link separates at 165°F (or 212°F where ambient temperatures run over 100°F) and closes the shutter automatically
- A governor controls how fast the shutter comes down during a fire
- AM640 in primed galvanized steel; AM641 in No. 4 stainless steel
- Compact box guides for a clean look
Specifications
| Models | AM640 (galvanized steel), AM641 (stainless steel); specified as Model 640 or 641 |
|---|---|
| Max width | 14′ (4.27 m) |
| Curtain | Interlocking flat slats, 1 1/2″ high, 22 gauge galvanized steel (AM640) or stainless steel (AM641) |
| Finish | AM640: primed galvanized steel in white, gray, tan or brown. AM641: No. 4 stainless steel |
| Fire labels | UL 3-hour Class A (masonry walls; FM optional) or UL 1 1/2-hour Class B (non-masonry walls) |
| Standard | NFPA 80 |
| Automatic closing | Fusible link at 165°F (212°F for ambient over 100°F), with governor-controlled descent |
| Guides | Compact box guides |
| Operation | Push-up; crank or electric optional |
| Lock | Slide bolt on push-up and crank shutters |
Options
- Time-delay release device: closes the shutter on alarm after a 10-second delay (up to 60 seconds, as allowed by the local authority)
- Fire-rated vision lites in 3-hour and 1 1/2-hour curtains
- UL-listed brush-type smoke seals
- 20-minute UL smoke label on shutters up to 12′ wide and 10′ high
- Photoelectric smoke detectors
- Crank or electric operation: electric operation needs no tension reset after a drop test or a power-loss closure
- Flame baffle (required for the FM label)
- Powder coating: four standard PowderGuard finishes; custom RAL colors (about 200) or color matching at additional cost (see powder coating)
Applications
The AM640 and AM641 protect counter openings in fire-rated walls in factories, schools, concessions, hospitals, cafeterias and retail settings. For a factory-assembled unit with its own frame and sill, see the AM660 and AM662. For counters that do not need a fire rating, see the AM650 series.
Frequently Asked Questions
What fire ratings are available?
A UL 3-hour Class A label for masonry fire walls, with an optional FM label, or a UL 1 1/2-hour Class B label for drywall and stud walls.
How does the shutter close in a fire?
A fusible link separates at 165°F (212°F where ambient temperatures run over 100°F), and a governor controls the descent. An optional time-delay release device can also close it when the fire alarm sounds.
What is the difference between the AM640 and AM641?
The curtain: primed galvanized steel (AM640) or No. 4 stainless steel (AM641).
How wide can it be?
Up to 14′ (4.27 m) wide.
Does it need drop testing?
Yes. NFPA 80 calls for fire-rated rolling doors and shutters to be drop tested and inspected every year. See our drop testing guide.